I-7021 ANALOG OUTPUT MODULE

FEATURES :

  • Current or Voltage Output
  • High Resolution: 12-bit
  • Software Selectable Current or Voltage Output
  • Open Wire Detection for Current Output
  • Read back Voltage or Current
  • Configurable Power-on Value
  • Programmable Output Slope

 

ModelI-7021
Communication
InterfaceRS-485
RS-485 Bias ResistorNo (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.)
Format(N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
Baud Rate1200 to 115200 bps
ProtocolDCON
Dual WatchdogYes, Module (1.6 Seconds), Communication (Programmable)
LED Indicator/Display
System LED IndicatorYes, 1 as Power/Communication Indicator
I/O LED Indicator
7-Segment LED Display
Isolation
Intra-Module Isolation3000 VDC
EMS Protection
ESD (IEC 61000-4-2)±4 kV Contact for each Terminal
EFT (IEC 61000-4-4)±4 kV to Power Line
Surge (IEC 61000-4-5)±0.5 kV for Power Line
Power
Reverse Polarity ProtectionYes
Input Range+10 ~ +30 VDC
Consumption1.8 W
Mechanical
Dimensions (L x W x H)123 mm x 72 mm x 35 mm
InstallationDIN-Rail or Wall Mounting
Environment
Operating Temperature-25 to +75°C
Storage Temperature-40 to +85°C
Humidity10 to 95% RH, Non-condensing

             10/286, G-2, Aarthi Flats, 1st Main Road, Neela Nagar, Medavakkam,

                                 Mobile : +91 99402225649884222563

                                                 Office : 044-22771356