I-7017 ANALOG INPUT MODULE
FEATURES :
- I-7017 8-channel Differential or 6-channel Differential and 2-channel Single-ended Analog Input
- Voltage and Current Input
- +/-120 VDC Overvoltage Protection
- High Resolution: 16-bit
- Open Wire Detection for 4 ~ 20 mA
Model | I-7017 |
Communication | |
Interface | RS-485 |
Format | (N, 8, 1) |
Baud Rate | 1200 ~ 115200 bps |
Protocol | DCON |
Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) |
LED Indicator/Display | |
System LED Indicator | Yes, 1 LED as Power/Communication Indicator |
I/O LED Indicator | – |
7-Segment LED Display | – |
Isolation | |
Intra-Module Isolation, | 3000 VDC |
Field-to-Logic | |
EMS Protection | |
ESD (IEC 61000-4-2) | +/- 2 kV Contact for each Terminal |
RS (IEC 61000-4-3) | +/- 4 kV for Power |
Power | |
Reverse Polarity Protection | Yes |
Input Range | 10 ~ 30 VDC |
Consumption | 1.3 W |
Mechanical | |
Dimensions (W x L x H) | 72 mm x 123 mm x 35 mm |
Installation | DIN-Rail or Wall Mounting |
Environment | |
Operating Temperature | -25 ~ +75°C |
Storage Temperature | -40 ~ +85°C |
Humidity | 10 ~ 95% RH, Non-condensing |
Storage Temperature | -40 to +85°C |
Humidity | 10 to 95% RH, Non-condensing |
10/286, G-2, Aarthi Flats, 1st Main Road, Neela Nagar, Medavakkam,
Mobile : +91 9940222564, 9884222563
Office : 044-22771356