I-7080 ENCODER/FREQUENCY/COUNTER INPUT
FEATURES :
- 2-channel Counter/Frequency Input
- 32-bit Counter
- Isolated or Non-isolated Input
- Programmable Alarm Output
- Programmable Digital Filter
- Programmable Threshold Voltage Level
- Maximum Frequency of up to 100 kHz
- Built-in Virtual Battery Backup to Preserve Counter Values
- Dual Watchdog
- Wide Operating Temperature Range: -25 ~ +75°C
Model | I-7080 |
Communication | |
Interface | RS-485 |
Format | (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
Baud Rate | 1200 ~ 115200 bps |
Protocol | DCON |
Dual Watchdog | Yes, Module (1.6 Seconds), Communication (Programmable) |
LED Indicator/Display | |
System LED Indicator | Yes, 1 LED as Power/Communication Indicator |
I/O LED Indicator | – |
7-Segment LED Display | – |
Isolation | |
Intra-Module Isolation, Field-to-Logic | 3000 VDC |
EMS Protection | |
ESD (IEC 61000-4-2) | ±4 kV Contact for each Terminal |
EFT (IEC 61000-4-4) | ±4 kV for Power Line |
Surge (IEC 61000-4-5) | ±0.5 kV for Power Line |
Power | |
Reverse Polarity Protection | Yes |
Input Range | 10 ~ 30 VDC |
Consumption | 2.0 W |
Mechanical | |
Dimensions (W x L x H) | 72 mm x 123 mm x 35 mm |
Installation | DIN-Rail or Wall Mounting |
Environment | |
Operating Temperature | -25 ~ +75°C |
Storage Temperature | -40 ~ +85°C |
Humidity | 10 ~ 95% RH, Non-condensing |